Electrical installation, Stop – Lenze EPZ-10202 User Manual
Page 16
![background image](/manuals/565989/16/background.png)
Electrical installation
Terminal assignment
EDK10202EZ3 DE/EN/FR 5.1
16
l
H1_E_INST−Belegung_10202_en
Terminal
Signal type
Function
Technical data
Remarks
X1/O5
Digital
outputs
LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Load capacity: max. 1
A
...
X1/O10
X2/I21
Digital
inputs
LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Input current: max. 8
mA at 24 V
X2/I22
X2/+O24
−
DC supply voltage
18 VDC ... 30 VDC
Connected via
emergency off at the
Drive PLC
X2/
^
24
−
GND, reference potential
X2/O11
Digital
outputs
LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Load capacity: max.
1 A
X2/O12
X3/I15
Digital
inputs
LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Input current: max. 8
mA at 24 V
...
X3/I20
X4/I9
...
X4/I14
(
Stop!
ƒ
Ensure a sufficient dimensioning of the DC voltage supply, if the loads are
connected to the digital outputs.
ƒ
The extension board must exclusively be supplied separately.The internal
supply via the Drive PLC is not permissible.