Switch position, Commissioning – Lenze E82ZAFSC100 User Manual

Page 41

Advertising
background image

Commissioning

Switch position

7

EDK82ZAFSC−100 DE/EN/FR 3.0

41

l

−H2−DIP−Schalter_Tabelle

Switch position

1

ON

2 3 4 5

ON

OFF

)

Note!

ƒ

Make sure to set the DIP switch and C0034 to the same range, otherwise
the analog input signal at X3/8 will be interpreted incorrectly by the basic
device.

ƒ

If a setpoint potentionmeter is supplied internally via X3/9, make sure to
set the DIP switch to the voltage range 0 ... 5 V. Otherwise it will be
impossible to cover the entire speed range.

Signal at X3/8

Switch position

C0034

1

2

3

4

5

0 ... 5V

OFF

OFF

ON

OFF

OFF

0

0 ... 10 V (Lenze setting)

OFF

OFF

ON

OFF

ON

0

0 ... 20 mA

OFF

OFF

ON

ON

OFF

0

4 ... 20 mA

OFF

OFF

ON

ON

OFF

1

4 ... 20 mA (open−circuit monitored)

OFF

OFF

ON

ON

OFF

3

−10 ... +10 V

ON

ON

OFF

OFF

OFF

2