Safety instructions

Residual hazards

1

l

10

EDK82EV303 EN 1.0

Device protection

ƒ

All pluggable terminals can only be plugged in or unplugged when the controller is
disconnected from the power supply!

ƒ

Frequent mains switching (e.g. inching mode via mains contactor) can overload and
destroy the input current limitation of the controller:
– Therefore at least 3 minutes must pass between two switch−on operations.

Motor protection

ƒ

Certain drive controller settings can overheat the connected motor:
– E. g. long−time operation of the DC injection brake.
– Long−time operation of self−ventilated motors at low speeds.

Protection of the machine/system

ƒ

Drives can reach dangerous overspeeds (e. g. setting of high output frequencies in
connection with motors and machines not suitable for this purpose):
– The drive controllers do not provide protection against such operating conditions.

For this purpose, use additional components.

J

Warnings!

ƒ

The device has no overspeed protection.

ƒ

Must be provided with external or remote overload protection.

ƒ

Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 240 V maximum (240 V devices) or 500 V maximum
(400/500 V devices) resp.

ƒ

Use 60/75 °C or 75 °C copper wire only.

ƒ

Shall be installed in a pollution degree 2 macro−environment.