Troubleshooting and fault elimination

Fault messages on the keypad or in the parameter setting program Global Drive Control

3

l

20

EDK82EV303 EN 1.0

3.3

Fault messages on the keypad or in the parameter setting program Global Drive Control

Keypad PC

1)

Fault

Cause

Remedy

noer

0

No fault

CCr

a

71

System failure

Strong interference injections on the
control cables

Shield control cable

Earth loops in the wiring

Ce0

a

61

Communication error
on AIF
(configurable in C0126)

Faulty transmission of control
commands via AIF

Insert the communication module properly
into the diagnosis terminal

Ce1

a

62

Communication error
on CAN−IN1 with sync
control

CAN−IN1 object receives faulty data or
communication is interrupted

l

Check plug connection of bus
module

ó FIF

l

Check sender

l

Increase monitoring time in C0357/1, if
necessary

Ce2

a

63

Communication error
on CAN−IN2

CAN−IN2 object receives faulty data or
communication is interrupted

l

Check plug connection of bus
module

ó FIF

l

Check sender

l

Increase monitoring time in C0357/2, if
necessary

Ce3

a

64

Communication error
on CAN−IN1 with event
or time control

CAN−IN1 object receives faulty data or
communication is interrupted

l

Check plug connection of bus
module

ó FIF

l

Check sender

l

Increase monitoring time in C0357/3, if
necessary

Ce4

a

65

BUS−OFF
(many communication
errors occurred)

Controller has received too many faulty
telegrams via the system bus and has
been disconnected from the bus

l

Check whether bus termination is
available

l

Check shield connection of the cables

l

Check PE connection

l

Check bus load, reduce the baud rate, if
necessary

Ce5

a

66

CAN time−out
(configurable in C0126)

In case of remote parameterisation via
the system bus (C0370):
Slave does not respond.
Communication monitoring time has
been exceeded

l

Check wiring of the system bus

l

Check system bus configuration

When operating with Application I/O:
Parameter set change−over has been
parameterised incorrectly

In all parameter sets, the "change parameter
set" signal (C0410/13, C0410/14) must be
connected with the same source

When operating with module on FIF:
Internal error

Contact Lenze

Ce6

a

67

System bus (CAN)
function module on FIF
has the "Warning" or
"BUS−OFF" status
(configurable in C0126)

CAN controller signals "Warning" or
"BUS−OFF" status

l

Check whether bus termination is
available

l

Check shield connection of the cables

l

Check PE connection

l

Check bus load, reduce the baud rate, if
necessary

Ce7

a

68

Communication error in
case of remote
parameterisation via
the system bus (C0370)
(configurable in C0126)

Node does not respond or is not
available

l

Check whether bus termination is
available

l

Check shield connection of the cables

l

Check PE connection

l

Check bus load, reduce the baud rate, if
necessary

When operating with Application I/O:
Parameter set change−over has been
parameterised incorrectly

In all parameter sets, the "change parameter
set" signal (C0410/13, C0410/14) must be
connected with the same source

EEr

a

91

External fault (TRIP−SET) A digital signal assigned to the TRIP−SET

function is activated

Check external encoder