7 multi-state input (msi) object descriptions, Multi-state input (msi) object descriptions, Bacnet objects – Lenze MCH Series Drives User Manual

Page 14

Advertising
background image

11

RG-MHBAC

BACnet Objects

4.7 Multi-State Input (MSI) Object Descriptions

Object MSI-1: Operational Status

This object is for monitoring the actual operating condition of the drive. The value returned
is a number between 1 and 16 which corresponds to one of the following operating states:

Value

Name

Operational State

1

LOCK

Fault Lockout

2

FAULT

Fault

3

PEND

Start Pending

4

STOP

Stop

5

BRAKE

DC Brake

6

RUN@0

Run At 0Hz

7

RUN

Run

8

ACCEL

Accelerating

9

DECEL

Decelerating

10

LIMIT

Current Limit

11

F DEC

Decel Override

12

INVAL

Invalid State

13

KSTOP

Keypad Stop

14

KSTOP

Alternate Keypad Stop

15

RSTOP

Remote (Terminal Strip) Stop

16

SSTOP

Serial Stop

Object MSI-2: Present Fault

This object indicates the type of fault on which the drive is currently tripped. This object
returns a value between 1 and 25 which corresponds to one of the following fault conditions:

Value Name

Fault

Value Name

Fault

1

NO FAULT

No Fault

14

CONTROL

Control Fault

2

OUTPUT

Output Fault

15

LANGUAGE

Language

3

E-STOP

E-Stop

16

EXTERNAL

External Fault

4

HI VOLTS

High DC Bus Volts

17

INTERNAL16 Internal Fault 16

5

HI TEMP

High Drive Temp

18

PWR TRAN

Power Transient

6

OVERLOAD Thermal Overload

19

INTERNAL18 Internal Fault 18

7

OUTPUT

Output Fault

20

INTERNAL19 Internal Fault 19

8

LO VOLTS

Low DC Bus Volts

21

INTERNAL20 Internal Fault 20

9

START ER

Start Error

22

INTERNAL21 Internal Fault 21

10

BRAKE ER

DC Brake Error

23

INTERNAL22 Internal Fault 22

11

FOLLOWER Follower Loss

24

INTERNAL23 Internal Fault 23

12

DB ERROR DB Error

25

SERIAL

Serial Comm Loss

13

PWR SAG

Power Sag

Advertising