background image

13

RG-MHBAC

BACnet Objects

State

Name Description

Reference

12

-VDC

0-10 VDC on TB-5A

(Closed loop setpoint control - PID Enabled)

13

-IDC

4-20 mA on TB-5B

(Closed loop setpoint control - PID Enabled)

14

SP#1

Preset Setpoint #1

(Closed loop setpoint control - PID Enabled)

15

SP#2

Preset Setpoint #2

(Closed loop setpoint control - PID Enabled)

16

SP#3

Preset Speed #3

(Open loop speed control - PID Enabled)

17

SP#4

Preset Setpoint #4

(Closed loop setpoint control - PID Enabled)

18

-MOP

Motor Operated Pot

(Closed loop setpoint control - PID Enabled)

19

-SER

Serial Setpoint Command

(Closed loop setpoint control - PID Enabled)

4.8 Multi-State Value (MSV) Object Descriptions

Object MSV-1: Speed Source Selection

This object mimics the functionality of the SPEED SOURCE key on the drive keypad. It
is used to determine whether the drive will get its speed/setpoint reference from Drive
Parameter #24 (Auto Source) or Drive Parameter #29 (Hand Source).

State

Name

Reference Source

1

NORMAL

Normal Source

2

HAND

Hand Source Only

3

AUTO

Auto Source Only

This object allows the user to toggle between OPEN loop speed control and CLOSED loop
PID control when PID mode is ENABLED (refer to MSI-3). The ability to command this
object through the LAN is dictated by Drive Parameter #30 (Control) and the drive HOA
(refer to MSI-4)