2 rated data, Rated data, Technical data – Lenze EZN3A0022H150N002 User Manual

Page 33

Advertising
background image

Technical data

Rated data

2

l

33

EDKZN3A150−002 DE/EN/FR 3.1

2.2

Rated data

Basis of the data

Mains

Voltage

Voltage range

Frequency range

U

Lrated

[V]

U

Lrated

[V]

f [Hz]

3/PE AC

400

320 − 0 % ... 440 + 0 %

45 − 0 % ... 65 + 0 %

3/PE AC

480

432 − 0 % ... 528 + 0 %

45 − 0 % ... 65 + 0 %

Type

Voltage

Frequency

Current [A]

Number of

phases

[V]

[Hz]

up to +40 °C



up to +55 °C



EZN3A0022H150
N002

400/480

50/60

150

93.8

3

 Temperature in the control cabinet

Power loss

Inductance

Voltage drop

P

loss

[W]

L [mH]

DU [V]

EZN3A0022H150N
002

340

0.22

10