Electrical installation
Mounting steps
l
42
EDKZN3A150−002 DE/EN/FR 3.1
4.4
Mounting steps
EZN−027
How to wire the filter:
1. Deenergise the control cabinet and fuse it against re−energisation.
2. Connect the connection cables "Load"
2 to the basic device.
– Observe the documentation for the basic device!
3. Mount the PE conductor to the PE stud
1 using the ring cable lug.
– Observe tightening torque!
4. Connect the mains cables "Line"
0 to the mains.
5. Wire the terminals of the thermal contact
3.
– Integrate the thermal contact into the monitoring system so that the mains supply
is switched off when the filter is overheated.
– NC contact, switching capacity: 250 V AC / 1.6 A
– Connect the twisted cables.
– Observe tightening torque.