2 rated data, Rated data, Technical data – Lenze ECSEKxxx User Manual
Page 44
Advertising

Technical data
Rated data
2
44
EDKCSEK002 DE/EN/FR 2.0
2.2
Rated data
Rated data
Type
ECSxK001xxx
ECSxK002xxx
Data for operation with upstream
supply module on mains voltage
U
mains
[V]
400
480
400
480
DC-bus voltage
U
DC
[V]
0 ... 770
Rated AC current
I
r
[A]
17,5
35
Rated power
P
B
[kW]
10
20
Rated power with mains choke
P
BN
[kW]
14
28
Capacity
C [
µ
F]
705 (
±
20 %)
1410 (
±
20 %)
Time constant for charging the
capacitors
τ
[ms]
150
Charging time after mains connection
t
C_charging
[s]
1
Weight
ECSEKxxx
m [kg]
2.1
3.2
ECSDKxxx
m [kg]
2.1
3.2
ECSCKxxx
m [kg]
2.4
3.4
Dimensions
ECSEKxxx
(W x H x D)
[mm]
88.5 x 247 x 176
132 x 247 x 176
ECSDKxxx
(W x H x D)
[mm]
88.5 x 247 x 176
132 x 247 x 176
ECSCKxxx
(W x H x D)
[mm]
88.5 x 282 x 123
132 x 282 x 123