Electrical installation – Lenze ECSEKxxx User Manual
Page 52

Electrical installation
Power terminals
4
52
EDKCSEK002 DE/EN/FR 2.0
Cable cross-sections and screw-tightening torques
Cable type
Wire end ferrule
Possible cable
cross-sections
Tightening torque
Stripping
length
Terminal strip X23
rigid
-
0.2 ... 10 mm
2
(AWG 24 ... 8)
1.2 ... 1.5 Nm
(10.6 ... 13.3 lb-in)
5 mm
flexible
without wire end ferrule
0.2 ... 10 mm
2
(AWG 24 ... 8)
with wire end ferrule
0.25 ... 6 mm
2
(AWG 22 ... 10)
with TWIN wire end
ferrule
0.25 ... 4 mm
2
(AWG 22 ... 12)
Shielded cables
The following factors decisively determine the effect of the shielded cables:
ƒ
Good shield connection
–
Ensure a contact surface as large as possible
ƒ
Low shield resistance
–
Only use shields with tin-plated or nickel-plated copper braids (shields
with steel braids cannot be used).
ƒ
High overlap rate of the braid
–
At least 70 ... 80 % with 90° overlap angle
The ECSZS000X0B shield mounting kit includes a wire clamp and shield sheet.