Safety instructions – Lenze EVF9333−xV User Manual

Page 19

Advertising
background image

Safety instructions

Safety instructions for the installation according to UL

2

l

19

EDKVF93−03 EN 3.0

Original − French

J

Warnings!

ƒ

Motor Overload Protection
– For information on the protection level of the internal overload protection

for a motor load, see the corresponding manuals or software helps.

– If the integral solid state motor overload protection is not used, external or

remote overload protection must be provided.

ƒ

Branch Circuit Protection
– The integral solid state protection does not provide branch circuit

protection.

– Branch circuit protection has to be provided externally in accordance with

corresponding instructions, the National Electrical Code and any
additional codes.

ƒ

Please observe the specifications for fuses and screw−tightening torques in
these instructions.

ƒ

EVF9330 … EVF9333 :
– Convient aux circuits non susceptibles de délivrer plus de 10000 ampères

symétriques eff., maximum 480 V, avec protection par fusibles.

– Convient aux circuits non susceptibles de délivrer plus de 50000 ampères

symétriques eff., maximum 480 V, avec protection par des fusibles de
calibre J, T ou R.

– Température ambiante maximale : 0 ... +50 °C
– > +40 °C: ramener le courant assigné de sortie à 2,5 %/°C
– Utiliser exclusivement des conducteurs en cuivre 60/75 °C ou 75 °C.

ƒ

EVF9330 … EVF9333 :
– Convient aux circuits non susceptibles de délivrer plus de 10000 ampères

symétriques eff., maximum 480 V, avec protection par fusibles.

– Convient aux circuits non susceptibles de délivrer plus de 50000 ampères

symétriques eff., maximum 480 V, avec protection par des fusibles de
calibre J, T ou R.

– Température ambiante maximale : 0 ... +50 °C
– > +40 °C: ramener le courant assigné de sortie à 2,5 %/°C
– Utiliser exclusivement des conducteurs en cuivre 60/75 °C ou 75 °C.