Troubleshooting and fault elimination, System error messages general error messages – Lenze EVF9333−xV User Manual

Page 43

Advertising
background image

Troubleshooting and fault elimination

System error messages

General error messages

4

l

43

EDKVF93−03 EN 3.0

Remedy

Cause

Description

Fault message

Remedy

Cause

Description

Display

No.

x062

CE1

Communication error on the
process data input object
CAN1_IN

CAN1_IN object receives faulty
data or communication is
interrupted.

l

Check wiring at X4.

l

Check sender.

l

Increase monitoring time
under C0357/1, if necessary.

l

Switch off monitoring
(C0591 = 3).

x063

CE2

Communication error on the
process data input object
CAN2_IN

CAN2_IN object receives faulty
data or communication is
interrupted.

l

Check wiring at X4.

l

Check sender.

l

Increase monitoring time
under C0357/2, if necessary.

l

Switch off monitoring
(C0592 = 3).

x064

CE3

Communication error on the
process data input object
CAN3_IN

CAN3_IN object receives faulty
data or communication is
interrupted.

l

Check wiring at X4.

l

Check sender.

l

Increase monitoring time
under C0357/3, if necessary.

l

Switch off monitoring
(C0593 = 3).

x065

CE4

BUS−OFF state of system bus
(CAN)

The controller has received too
many faulty telegrams via the
system bus (CAN) and has
disconnected from the bus.

l

Check wiring at X4: Is the bus
correctly terminated?

l

Check shield connection of the
cables.

l

Check PE connection.

l

Check bus load, reduce the
baud rate if necessary.
(Observe the cable length!)

l

Switch off the monitoring
(C0595 = 3).

0071

CCr

System failure

Strong interference injection on
the control cables

Screen control cables

Ground or earth loops in the
wiring

l

Check wiring

l

Check PE connection

After troubleshooting: Deenergise
the device completely (disconnect
24 V supply, discharge DC bus)!

0072

PR1

Checksum error in parameter
set 1
CAUTION: The Lenze setting is
loaded automatically!

l

Fault when loading a
parameter set.

l

Interruption while
transmitting the parameter set
via keypad.

l

Set the required parameters
and store them under C0003 =
1.

l

As to PLC devices, check the
use of pointers.

The stored parameters are
incompatible with the loaded
software version.

Store the parameter set under
C0003 = 1 first to allow for a
faults reset.

0073

PR2

Checksum error in parameter
set 2
PLEASE NOTE: The Lenze setting is
loaded automatically!

l

Fault while loading a
parameter set.

l

Interruption during the
transfer of the parameter set
via keypad.

l

Set the required parameters
and save them with C0003 = 2.

The parameters saved do not
comply with the software version
loaded.

In order to be able to
acknowledge the error, first save
the parameter set with C0003 = 2.