Electrical installation

Terminal assignment

4

l

65

EDBPM−H505 DE/EN/FR 6.1

4

Electrical installation

4.1

Terminal assignment

(

Stop!

ƒ

Damage of units connected. Connect the PE conductor as shown
in the figure!

ƒ

Wire the operating unit only when no voltage is applied!

INPUT VOLTAGE: 18-32 VDC 10 W
FUSE 800 mA

+24 VDC

0 VDC

1

2

3

4

N. C.

M

SP

N.C.

CAN+

Shield

CAN-

V-

1 2 3 4 5

CAN-GND

CAN-LO

CAN-HI

~

PE

N

L1

+18…32VDC

12

3

4

h505_001

Fig. 4−1

Assignment of the terminals

DC supply voltage

Terminal

Identification

Explanation

1

DC +24 V

Supply voltage (DC +18 V ... 32 V)

2

DC 0 V

GND supply voltage, reference potential

3

n.c.

not connected

4

PE potential

System bus (CAN)

Terminal

Identification

Explanation

1

V−

GND

Reference potential

2

CAN−

LO

System bus LOW (data line)

3

Shield

Apply shield of the system bus cable

4

CAN+

HI

System bus HIGH (data line)

5

n.c.

not connected