Residual hazards, Safety instructions – Lenze EZN3B series User Manual

Page 30

Advertising
background image

Safety instructions

Residual hazards

2

l

30

EDKZN3B024 DE/EN/FR 3.0

2.2

Residual hazards

{

Danger!

Dangerous electrical voltage

All power terminals remain live for up to three minutes after mains
disconnection.

Possible consequences:

ƒ

Death or severe injuries when touching the power terminals.

Protective measures:

ƒ

Switch off the power supply and wait for at least three minutes
before working on the power terminals.

ƒ

Make sure that all power terminals are deenergised.

{

Danger!

Hazardous electrical voltage

The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:

ƒ

Death or severe injuries when touching the device in the event of
an error.

Protective measures:

Implement the measures required in EN 61800−5−1. Especially:

ƒ

Fixed installation
– Implement PE connection in compliance with standards.
– Connect PE conductor twice or PE conductor cross−section

³ 10 mm

2

.

ƒ

Connection with a connector for industrial applications according
to IEC 60309 (CEE):
– PE conductor cross−section

³ 2.5 mm

2

as part of a multi−core

supply cable.

– Provide for suitable strain relief.