Electrical installation

Connection data

6

l

45

EDKZN3B024 DE/EN/FR 3.0

6.3

Connection data

[mm

2

]

[AWG]

[mm]

[Nm]

[

lb−in]

EZN3x2400H002

0.2 ... 4

0.25 ... 4

0.5 ... 1.5

24 ... 10

8

0.6 ... 0.8
5.3 ... 7.1

EZN3x1500H003

EZN3x0900H004

EZN3x0750H005

EZN3x0500H007

EZN3x0400H009

EZN3x0300H013

EZN3x0250H015

0.2 ... 6

0.25 ... 6

0.5 ... 4

24 ... 8

9

1.5 ... 1.8

13.2 ... 15.9

EZN3x0150H024

6.4

Mounting steps

EZN−055

How to wire the filter:
1. Deenergise the control cabinet and fuse it against re−energisation.
2. Connect the connection cables of the standard device to terminal "Load"

2.

Observe the documentation of the standard device!

3. Connect the mains cables to terminal "Line"

0.

Observe tightening torque!