Rated data, Technical data – Lenze EZN3B series User Manual

Page 37

Advertising
background image

Technical data

Rated data

4

l

37

EDKZN3B024 DE/EN/FR 3.0

4.2

Rated data

Mains

Voltage

Voltage range

Frequency range

U

Lrated

[V]

U

Lrated

[V]

f [Hz]

3/PE AC

400

320 − 0 % ... 440 + 0 %

45 − 0 % ... 65 + 0 %

3/PE AC

480

432 − 0 % ... 528 + 0 %

45 − 0 % ... 65 + 0 %

Type

Voltage

Frequency

Current [A]

Number

of phases

[V]

[Hz]

up to +40 °C

 up to +55 °C 

EZN3x2400H002

400/480

50/60

1.5

0.9

3

EZN3x1500H003

400/480

50/60

2.5

1.6

3

EZN3x0900H004

400/480

50/60

4.0

2.5

3

EZN3x0750H005

400/480

50/60

5.0

3.1

3

EZN3x0500H007

400/480

50/60

7.0

4.4

3

EZN3x0400H009

400/480

50/60

9.0

5.6

3

EZN3x0300H013

400/480

50/60

13.0

8.1

3

EZN3x0250H015

400/480

50/60

15.0

9.4

3

EZN3x0150H024

400/480

50/60

24.0

15.0

3

 Temperature in the control cabinet

Power loss

Inductance

Voltage drop

P

loss

[W]

L [mH]

DU [V]

EZN3x2400H002

17

24

20

EZN3x1500H003

18

15

20

EZN3x0900H004

28

9.0

20

EZN3x0750H005

32

7.5

20

EZN3x0500H007

39

5.0

20

EZN3x0400H009

49

4.0

20

EZN3x0300H013

53

3.0

20

EZN3x0250H015

75

2.5

20

EZN3x0150H024

90

1.5

20

Advertising