Wiring, Electrical installation – Lenze EMF2141IB 2141 LON User Manual
Page 32

4
Electrical installation
Wiring
EDKMF2141 DE/EN/FR 2.0
L
32
Wiring to a host
)
)
)
)
Note!
An additional mains isolation is required, if
l
a 820X or 821X controller is connected to a host and
l
a safe mains isolation (double basic insulation) is required according to
VDE 0160.
For this, it is, for instance, possible to use an interface module which
provides an additional mains isolation (see corresponding manufacturer’s
data).
For wiring, the electrical isolation of the supply voltage must be taken into
account.
Cable specification
-14-
Please follow the recommendations for signal cables of the Echelon Corporationr.
Cable resistance
92 - 108
Ω
/km (f = 64 kHz - 1 MHz)
Capacitance per unit length
≤
55.9 nF/km
Loop resistance
14.0 - 15.5
Ω
/km
Cable diameter
0.5 mm
2
- 1.5 mm
2
(24 AWG - 16 AWG)
Wires
Twisted in pairs
)
)
)
)
Note!
For more cable speicifications see LonWorks
â
FTT-10A Free Topology
Transceiver User’s Guide:
l
TIA568A Category 5, 24 AWG
l
NEMA Level IV, 22 AWG