Technical data

General data and operating conditions

EDKCSZZ040 DE/EN/FR 3.1

36

l

H1_Daten−Verlustleist_ECSZZ

4

Technical data

General data and operating conditions

Standards

Approval

UL 1283

Standard for Electromagnetic Interference Filters (File
No. E70122) for USA

Mains data

Mains types

With grounded neutral (TT/TN systems)

Operation permitted without restrictions

Other mains types

Observe instructions for special measures in the
documentation for the basic device!

Protection

Type of protection

EN 60529

IP 20

Not in the wire range of
the terminals

NEMA 250

Protection against contact to
type 1

Insulation resistance

EN 61800−5−1

Overvoltage category III
> 2000 m: Overvoltage category II

Leakage current

EN 61800−5−1

> 3.5 mA

Observe regulations
and safety instructions!

Ambient conditions

Temperature

Storage

−25 ... +60 °C

Transport

−25 ... +70 °C

Operation

−10 ... +55 °C
Current derating from +40 to +55 °C: 2.5 %/°C

Site altitude

0 ... 4000 m amsl
1000 ... 4000 m amsl: Current derating by 5 %/1000 m

Pollution

EN 61800−5−1

Pollution degree 2

Vibration resistance

EN 50178; IEC
61800−5−1;
Germanischer
Lloyd, general
conditions

Acceleration−resistant up to 1 g