Electrical installation

Important notes

EDKCSZZ040 DE/EN/FR 3.1

42

l

H1_E_INST−WiHi_ElekInst_PE

6

Electrical installation

Important notes

ƒ Installation must

– always be in accordance with the operating conditions specified in the Technical

data (

^ 36).

– be carried out to EN 60204−1.

ƒ Please observe the following when selecting the cable type:

– The cables used must comply with the approvals required for the application (e. g.

VDE, UL etc.).

– Fuses and cable cross−sections must be dimensioned in accordance with the

specifications in the documentation for the basic device.

ƒ Please observe the following when laying the cables between RFI filter and supply

module:
– Cable length < 30 cm: use unshielded cables
– Cable length > 30 cm: use shielded cables and keep them as short as possible.

ƒ Please observe the following when laying the mains cables:

– Mains cables and ±UG cables must not touch each other.
– When laying mains cables and ±UG cables in parallel keep a distance >150 mm

between the cables.

ƒ Please observe the following when laying the PE cable:

– The PE connection must comply with EN 61800−5−1.