Electrical installation
Mounting steps
EDKCSZZ040 DE/EN/FR 3.1
45
l
H2_Anschl_dat−−−−(DUMMYSEITEVOR)−−−
Mounting steps
ECSZZ005
Fig. 6
Filter connections
How to connect the filter:
1. Disconnect the control cabinet from the mains and protect against power−on.
2. Connect the filter output cables (X11) to terminal X21 of the ECSxE... supply module.
– Observe the documentation for the ECSxE... supply module.
3. Connect the mains cables to terminal X10.
– Observe tightening torque.
4. Attach PE conductor to PE screw using a ring cable lug.
– Observe tightening torque.