Technical data

Rated data

2

l

33

EDKZNXXXX−001 DE/EN/FR 3.0

2.2

Rated data

Basis of the data

Mains

Voltage

Voltage range

Frequency range

U

Lrated

[V]

U

Lrated

[V]

f [Hz]

3/PE AC

400

320 − 0 % ... 440 + 0 %

45 − 0 % ... 65 + 0 %

3/PE AC

480

432 − 0 % ... 528 + 0 %

45 − 0 % ... 65 + 0 %

Type

Voltage

Frequency

Current [A]

Number of

phases

[V]

[Hz]

up to +40 °C



up to +55 °C



EZN3x0022H150

400/480

50/60

150

93.8

3

EZN3x0017H200

400/480

50/60

200

‚

125

3

EZN3x0015H230

400/480

50/60

230

144

3

 Temperature in the control cabinet

‚ up to 35 °C: 213 A

Power loss

Inductance

Voltage drop

P

loss

[W]

L [mH]

DU [V]

EZN3A0022H150
EZN3B0022H150

340
330

0.22

10

EZN3A0017H200
EZN3B0017H200

340
320

0.17

10

EZN3A0015H230
EZN3B0015H230

350
340

0.15

10