Electrical installation

Mounting steps

4

l

42

EDKZNXXXX−001 DE/EN/FR 3.0

4.4

Mounting steps

EZN−027

How to wire the filter:

1. Deenergise the control cabinet and fuse it against re−energisation.

2. Connect the connection cables "Load"

2 to the basic device.

– Observe the documentation for the basic device!

3. Mount the PE conductor to the PE stud

1 using the ring cable lug.

– Observe tightening torque!

4. Connect the mains cables "Line"

0 to the mains.

5. Wire the terminals of the thermal contact

3.

– Integrate the thermal contact into the monitoring system so that the mains supply

is switched off when the filter is overheated.

– NC contact, switching capacity: 250 V AC / 1.6 A
– Connect the twisted cables.
– Observe tightening torque.