6.6.3
Continuous counting
Function:
The counter starts counting from the start value in the counting range.
If the counter reaches the upper counting limit value when counting up and another
count pulse in the positive direction is issued, the counter jumps to the lower counting
limit value and continues counting from there.
If the counter reaches the lower counting limit value when counting down and another
count pulse in the negative direction is issued, the counter jumps to the upper counting
limit value and continues counting from there.
If this function is activated, a process alarm is triggered if the value exceeds or falls
below a limit value.
[6.1]
Example of "Continuous counting"
Limits
Counting range
Lower counting limit -2 147 483 648 (-2
31
)
Upper counting limit +2 147 483 647 (-2
31
-1)