10 function of the hysteresis, L-force controls | i/o system 1000 – Lenze L-force I/O System 1000 User Manual
Page 57

2.0 EN - 11/2010
L
57
L-force Controls | I/O System 1000
Parameter setting
Electronic modules - counters
6.6.10
Function of the hysteresis
Count value ≥ comparison value
The hysteresis is activated if the comparison condition is met. When the hysteresis is
activated, the comparison result remains unchanged until the count value drops out of the
set hysteresis range. After the count value has exited the hysteresis range, the comparison
conditions must be met once more for the hysteresis to be activated again.
c
Count value ≥ comparison value: Output is set and hysteresis is activated
d
Hysteresis range is exited: Output is reset
e
Count value ≥ comparison value: Output is set and hysteresis is activated
f
Hysteresis range is exited, output remains set because count value ≥ comparison value
g
Count value < comparison value and hysteresis is active: Output is reset
h
Count value ≥ comparison value: Output is not set because hysteresis is activated
i
Hysteresis range is exited, output is set because count value ≥ comparison value