2 heartbeat protocol, L-force controls | i/o system 1000 – Lenze L-force I/O System 1000 User Manual
Page 91

2.0 EN - 11/2010
L
91
L-force Controls | I/O System 1000
Error management
Monitoring
8.1.2
Heartbeat protocol
[8-1]
Heartbeat protocol
Heartbeat producer
The I/O system 1000 transmits a status telegram to the fieldbus and can thus be
monitored by other nodes.
The settings are made in index 0x1017.
Producer heartbeat is started automatically if a time > 0 is entered in index 0x1017 and
the I/O system 1000 changes to Operational.
After the cycle time has elapsed, the status telegram is transferred from the I/O
system 1000 to the fieldbus.
A reset takes place by a change to Operational.
r: reserved (always 0)
s: Status of the heartbeat producer
COB-ID = 1792 + Node-ID
Heartbeat
Consumer
Heartbeat
Producer
indication
indication
indication
indication
indication
indication
indication
indication
Heartbeat Event
request
request
Heartbeat
Producer
Time
Heartbeat
Consumer
Time
Heartbeat
Consumer
Time
0
0
1
1
r
r
s
s
7
7
6 … 0
6 … 0