L-force Controls | I/O System 1000
Networking via CAN system bus
Configuring the network
82
L
2.0 EN - 11/2010
7.3.2
Monitoring tab
The Monitoring tab serves to set responses that are to be executed in case of
communication faults.
Settings are immediately active after the transfer.
7.3.3
Diagnostics tab
The Diagnostics tab serves to check the node address of the CAN bus coupler module.
The node address in the Address input field must comply with the node address in the
Node-ID display field. Otherwise you have to change the node address in the Address
input field.
– The node address in the Address input field is only important for the configuration
within the »Engineer«.
– The node address in the Node-ID input field presents the setting of the coding switch
at the CAN bus coupler module.
Legend
Selection
Description
Index
LENZE PDO Control 1
...
LENZE PDO Control 10
0 ... 65535 ms
Monitoring time for the receive objects (RPDO).
The I/O system 1000 changes to Pre-Operational
if no RPDO has been received within the set time.
0x2400/1
...
0x2400/10