Technical Information

TI.227-02

OUTSIDE AIR HUMIDITY & TEMP SENSOR

Page 2 of 4

HU-227 humidity transducers are 4-20 mA output units powered

with a 12-40 VDC supply.

The following describes the proper wiring of these humidity and

temp sensors with mA output:

HUMIDITY SENSOR:
1. Remove the terminal block by carefully pulling it off the circuit

board.

2. Locate the [+] and [-] terminal markings on the board.

3. Attach the supply voltage to the [+] lead.

4. Connect the 4-20 mA output ([-] terminal) to the controller’s

input terminal.

5. Ensure that the power supply common is attached to the

common bus of the controller.

6. Re-insert the terminal block to the circuit board and apply

power to the unit.

7. Check for the appropriate output signal using a DVM set on

DC milliamps connected in series with the [-] terminal.

RoHS

Mounting

HU-227 - Refer to Figure 7 for mounting

dimensions.

1. Choose a mounting location so that the unit

is protected from direct sunlight, rain & snow.
2. Mount transducer on a vertical surface with

two #8 self-tapping screws (not provided).
3. Pull wires through knockout & make neces-

sary connections (see wiring diagrams).
4. Replace cover and tighten Philips screws.

Wiring

Use maximum 12 AWG wire for wiring terminals.

Refer to

Figures 2, 3, 5 & 6 for wiring informa-

tion and

Figure 4 for dip switch designations.

Wiring HU-227 Units with mA Output

Figure 1 - HU-227 Humidity Transducer with mA Output

mA Output

TEMP SENSOR:
1. Remove the terminal block by carefully pulling it off the circuit

board.

2. Use shielded 18-22 AWG wire to connect temp sensor as

shown in

Figures 2 & 3.

INSTALLATION

Inspection

Requirements

Inspect the package for damage. If damaged,

notify the appropriate carrier immediately. If

undamaged, open the package and inspect the

device for obvious damage. Return damaged

products.

• Tools (not provided):
-- Digital Volt-ohm Meter (DVM)
-- Appropriate screwdriver for mounting

screws
-- Appropriate drill and drill bit for mounting

screws

• Appropriate accessories

• Two #8 self-tapping mounting screws (not

provided)

• Training: Installer must be a qualified,

experienced technician

Warning:

• Do not use on oxygen service, in an explosive/

hazardous environment, or with flammable/

combustible media.
• Disconnect power supply before installation to

prevent electrical shock and equipment damage.
• Make all connections in accordance with the job

wiring diagram and in accordance with national and

local electrical codes. Use copper conductors only.

Caution:

• Use electrostatic discharge precautions (e.g., use

of wrist straps) during installation and wiring to

prevent equipment damage.
• Avoid locations where severe shock or vibration,

excessive moisture or corrosive fumes are present.

NEMA Type 4 housings are intended for outdoor

use primarily to provide a degree of protection

against wind-blown dust, rain, and hose-directed

water.
• Do not exceed ratings of the device.