Model HU-227

Technical Information

TI.227-02

Page 4 of 4

CHECKOUT

DIMENSIONAL DATA

1. Verify that the unit is mounted in the correct position.

2. Verify appropriate input signal and supply voltage.

3. Verify appropriate configuration range.

CAUTION: Never connect 120 VAC to these transducers.

Never connect AC voltage to a unit intended for DC supply.

Transducer

Operation

MAINTENANCE

Regular maintenance of the total system is recom-

mended to assure sustainted optimum performance.

FIELD REPAIR

None. Replace with a functional unit.

WARRANTY

See Data Sheet for additional information.

Figure 7 - HU-227 Outside Air Humidity & Temp Sensor

dimensions shown in inches and millimeters (mm).

RoHS

TI.227-02

OUTSIDE AIR HUMIDITY & TEMP SENSOR

TYPICAL APPLICATIONS (wiring diagrams)

Neutral

Hot

+

Controller / Meter / Recorder

VDC Output Transducer Only

12-35 VAC Transformer

Figures 5 & 6 illustrate typical wiring diagrams for the HU-227,

0-5/0-10 VDC output humidity transducers.

Figure 5 - Wiring for VDC Output when applied with External AC

Supply

Figure 6 - Wiring for VDC Output when applied with External DC

Power Supply

Signal

+

Common

Supply

O

+

Controller / Meter / Recorder

VDC Output Transducer Only

12-40 VDC Power Supply

Input Signal

+

Common
Shield/Ground

Temp
Input

Input Signal

+

Common
Shield/Ground

Temp
Input

Humidity

Temp

Signal

+

Common

Supply

O

Humidity

Temp

NOTE: The HU-227 is a highly accurate device. For applica-
tions requiring a high degree of accuracy, the use of laboratory-
quality meters and calibration standards are recommended.

Calibration of HU-227 mA/VDC Humidity Transducer
Field calibration instructions are provided with the following precautions

and advice:
1. Do not verify comparative RH with a sling Psychrometer. There are far

too many variables which induce errors into this process. New HU-227

RH transducers are calibrated to NIST standards.

2. Recalibration must be done in a controlled environment. Relative

humidity must be held stable while making any adjustment.
3. Verify the output from the device directly with calibrated instrumenta-

tion and verify the RH with calibrated instrumentation, (NOT A

CONTROLLER OUTPUT). With the correct power applied and only a

meter connected to the output of the transducer, insure that the output

is proportional to the true RH.
4. A)

SINGLE POINT CALIBRATION: [NOTE: SELECT EITHER

OPTION 1

OR OPTION 2, BUT NOT BOTH.]

Option 1: Select a controlled humidity environment between 10 & 40%

RH. Insure humidity is stable and adjust zero trimmer (Z).

Option 2: Select a controlled humidity environment between 40 & 70%

RH. Insure humidity is stable and adjust span trimmer (S).

B)

TWO POINT CALIBRATION: Select a controlled humidity environ-

ment between 10 & 40% RH. Insure humidity is stable and adjust zero

trimmer (Z). Then select a controlled humidity environment between

70 & 75% RH. Insure humidity is stable and then adjust span trimmer (S).

CALIBRATION All units are factory calibrated to meet or exceed

published specifications. If field adjustment is necessary, follow

the instructions below.