Model HU-227

Technical Information

TI.227-02

OUTSIDE AIR HUMIDITY & TEMP SENSOR

Page 3 of 4

+

Controller / Meter / Recorder

mA Output Transducer Only

Figure 3 - Wiring for mA Output Humidity Transducer where

Controller or Meter has Internal DC Power Supply

RoHS

HU-227 humidity transducers with VDC output are field selectable

0-5 VDC or 0-10 VDC output and can be powered with either

12-40 VDC or 12-35 VAC.

The following describes the proper wiring of these humidity

transducers with VDC output:

Wiring HU-227 Units with VDC Output

0 to 10 VDC

(Factory Default)

0 to 5 VDC

Figure 4 - HU-227 Humidity Transducer with VDC Output

VDC Output

Humidity

Temp

Input Signal

+

Common
Shield/Ground

Temp
Input

HUMIDITY SENSOR:
1. Remove the terminal block by carefully pulling it off the circuit

board.

2. Locate the [+], [-] and [O] terminal markings on the board.

3. Attach the power wires to the [+] and [-] terminals. The [-]

terminal is also the negative output terminal.

4. Connect the [O] terminal, which is the positive VDC output

terminal, to the controller’s input terminal.

5. Re-insert the terminal block to the circuit board and apply

power to the unit.

6. Check the appropriate VDC output using a voltmeter set on DC

volts across the [O] and [-] terminals.

TEMP SENSOR:
1. Remove the terminal block by carefully pulling it off the

circuit board.

2. Use shielded 18-22 AWG wire to connect temp sensor as

shown in

Figures 5 & 6.

Caution: If you are using grounded AC, the hot wire must

be on the [+] terminal. Also, if you are using a controller

without built-in isolation, use an isolation transformer to

supply the HU-227 transducer.

Caution: This product contains a half-wave rectifier power

supply and must not be powered off transformers used to

power other devices utilizing non-isolated full-wave rectifier

power supplies.

Caution: When multiple units are powered from the same

transformer, damage will result unless all 24G power leads

are connected to the same power lead on all devices. It is

mandatory that correct phasing be maintained when power-

ing more than one device from a single transformer.

TYPICAL APPLICATIONS (wiring diagrams)

Input Signal

+

Common

+

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

12-40 VDC Power Supply

Figures 2 & 3 illustrate typical wiring diagrams for the HU-227,

4-20 mA two wire humidity transducers.

Figure 2 - Wiring for mA Output Humidity Transducer with

External DC Power Supply

Humidity

Temp

Temp
Input