Resetting the Thermal Overloads

Model 505.20 - 505.30 SilentFlo™ HPU

Operation

45

A tripped thermal overload or a blown fuse indicates a potential short circuit, too
much heat in the electrical box, or a component failure (mechanical or electrical).

To reset the thermal overload switches or replace the fuses:

1. Turn the main disconnect switch counterclockwise to remove power from

the electrical control box.

2. Loosen the two bolts securing the door of the electrical enclosure and open

the door.

3. Locate the thermal overload switch. Press the Reset button to clear the

switch. If thermal overload switch trips again, wait until it cools.

Transformer
Fuses
FU4—FU6

Line Fuses
FU1—FU3

Thermal
Overload