Series f continuous flex control cables – Northern Connectors Alpha Wire Communication, Control & Industrial Cable User Manual

Page 6

Advertising
background image

Alpha Wire | www.alphawire.com | 1-800-52 ALPHA

Specifications subject to change. For complete specifications and availability, visit www.alphawire.com.

278

Cable > Communication, Control and Industrial > Multiconductor > Unshielded > 600 V

Series F Continuous Flex Control Cables

High-Flex Cable Track Applications

600 V Unshielded, Multiconductor

UL TC-ER, PLTC

UL TFFN (18 – 16 AWG)

UL THHN (14 – 8 AWG)

CSA AWM I/II A/B FT4

CE LVD 73/23/EEC Amend.

93/68/EEC

Operating Temperature

• -25°C to +90°C (static)

• -5°C to +90°C (dynamic)

Conductor Color Coding

• Red, blue, or black insulation*,

numbered

1 green/yellow green conductor

1 white-striped neutral

(12 conductors or greater,

except 14 AWG)

Materials

• Stranded bare copper

conductors

• PVC/nylon insulation

• Black oil-resistant thermoplastic

elastomer jacket

Features

• UL Sunlight Resistant

• UL Oil Res. I/II

• 10x bend radius

• Over 20 million rolling flex cycles

• Tic-tock and twist test per

MIL-C-13777G

• Suitable for use in Class I,

Division 2 locations per Article

501 of the National Electric Code

Availability

Bulk, cut to length

FIT® Tubing Recommendations

• FIT-600: Highly flexible,

cross-linked elastomer

• FIT-650: Chemical- and

temperature-resistant

fluoroelastomer

14 AWG (2.11 mm

2

)

Stranding: 105/34 (105 x 0.16 mm)

Insulation thickness: 0.016 (0.41 mm) PVC/0.005 (0.10 mm) nylon

Part No.

Conductors

Nominal

Diameter

Jacket

Thickness

Black Insul.

Blue Insul.

Red Insul.

Inch

mm

Inch

mm

F14004KW F14004LW F14004RW

4

0.398

10.11

0.050

1.27

F14005KW F14005LW

F14005RW

5

0.434

11.02

0.050

1.27

F14007KW F14007LW

F14007RW

7

0.539

13.69

0.065

1.65

F14012KW

F14012LW

F14012RW

12

0.628

15.95

0.065

1.65

12 AWG (3.38 mm

2

)

Stranding: 168/34 (168 x 0.16 mm)

Insulation thickness: 0.016 (0.41 mm) PVC/0.005 (0.10 mm) nylon

Part No.

Conductors

Nominal

Diameter

Jacket

Thickness

Black Insul.

Blue Insul.

Red Insul.

Inch

mm

Inch

mm

F12004KW F12004LW

F12004RW

4

0.501

12.73

0.065

1.65

F12005KW F12005LW

F12005RW

5

0.545

13.84

0.065

1.65

F12007KW F12007LW

F12007RW

7

0.640

16.26

0.065

1.65

10 AWG (5.32 mm

2

)

Stranding: 105/30 (105 x 0.25 mm)

Insulation thickness: 0.022 (0.56 mm) PVC/0.005 (0.10 mm) nylon

Part No.

Conductors

Nominal

Diameter

Jacket

Thickness

Black Insul.

Blue Insul.

Red Insul.

Inch

mm

Inch

mm

F10004KW F10004LW F10004RW

4

0.565

14.35

0.065

1.65

F10005KW F10005LW F10005RW

5

0.618

15.70

0.065

1.65

F10007KW F10007LW

F10007RW

7

0.729

18.52

0.065

1.65

8 AWG (8.51 mm

2

)

Stranding: 168/30 (168 x 0.25 mm)

Insulation thickness: 0.032 (0.81 mm) PVC/0.006 (0.15 mm) nylon

Part No.

Conductors

Nominal

Diameter

Jacket

Thickness

Black Insul.

Blue Insul.

Red Insul.

Inch

mm

Inch

mm

F08004KW F08004LW F08004RW

4

0.740

18.80

0.065

1.65

* Red insulation: AC circuits operating at less than line voltage

Blue insulation: DC circuits operating at less than line voltage

Black insulation: AC circuits operating at less than line voltage

Advertising