Alpha Wire | www.alphawire.com | 1-800-52 ALPHA

Specifications subject to change. For complete specifications and availability, visit www.alphawire.com.

367

Cable > Communication, Control and Industrial > Multipair > Individual and Overall Shield > 300 V

Communication and Control

300 V Individually Foil Shielded Pairs or Overall Foil Shielded,

Multipair, FPP, PVC

Individually Foil Shielded Pairs

24 AWG (0.23 mm

2

)

Stranding: 7/32 (7 x 0.20 mm)

Insulation thickness: 0.023 (0.58)

Part No.

Conductors

Nominal Diameter

Jacket Thickness

AWM

Inch

mm

Inch

mm

6073C

3

0.374

9.50

0.048

1.22

2493

6076C

6

0.483

12.27

0.048

1.22

2493

6079C

9

0.597

15.16

0.065

1.65

2493

6079/11C

11

0.643

16.33

0.065

1.65

2493

6079/12C

12

0.663

16.84

0.065

1.65

2493

6079/15C

15

0.719

18.26

0.065

1.65

2493

6079/27C

27

0.962

24.43

0.087

2.21

2490

Characteristic impedance: 115 ohms

Mutual capacitance: 12 pF/ft (41 pF/m)

Overall Foil Shield

22 AWG (0.32 mm

2

)

Stranding: Solid

Insulation thickness: 0.023 (0.58)

Part No.

Conductors

Nominal Diameter

Jacket Thickness

AWM

Inch

mm

Inch

mm

6072C*

2

0.42

9.50

0.035

0.89

2668

Characteristic impedance: 150 ohms

Mutual capacitance: 8.8 pF/ft (28.9 pF/m)

UL AWM 2490, 2493, 2668

VW-1

UL CM

CSA CMG FT4

Operating Temperature

• -20°C to +75°C (CM)

• -20°C to +60 (AWM, CMG)

Conductor Color Coding

• Chart K (page 517)

Materials

• Solid or stranded tinned

copper conductors

• Foam polypropylene insulation

• Individual aluminum/polyester

foil shield, 25% overlap min.

Foil facing inward

Stranded tinned copper drain

wire, 24 AWG (0.23 mm

2

),

7/32 (7 x 0.20 mm)

• Slate PVC jacket (unless

otherwise noted)

Availability

100 ft (30.5 m)

500 ft (152 m)

1000 ft (305 m)

*Black jacket.