Communication and control, 300 v overall foil shield, multipair, sr-pvc, pvc – Northern Connectors Alpha Wire Communication, Control & Industrial Cable User Manual

Page 66

Advertising
background image

Alpha Wire | www.alphawire.com | 1-800-52 ALPHA

Specifications subject to change. For complete specifications and availability, visit www.alphawire.com.

338

Cable > Communication, Control and Industrial > Multipair > Overall Foil Shield > 300 V

Communication and Control

300 V Overall Foil Shield, Multipair, SR-PVC, PVC

UL AWM 2464

UL CM

CSA CMG FT4

Operating Temperature

• -20°C to +80°C (AWM)

• -20°C to +75°C (CM)

• -20°C to +60°C (CMG)

Conductor Color Coding

• Chart K (page 517)

Materials

• Stranded tinned copper

conductors

• Semirigid PVC insulation

• Aluminum/polyester foil shield,

25% overlap min.

Foil facing inward

Stranded tinned copper drain

wire equal in size to conductor

• Slate PVC jacket

Availability

100 ft (30.5 m)

500 ft (152 m)

1000 ft (305 m)

24 AWG (0.23 mm

2

)

Stranding: 7/32 (7 x 0.20 mm)

Insulation thickness: 0.010 (0.25 mm)

Part No.

Pairs

Nominal Diameter

Jacket Thickness

Inch

mm

Inch

mm

5471C

1

0.156

3.96

0.032

0.81

5472C

2

0.212

5.38

0.032

0.81

5473C

3

0.224

5.69

0.032

0.81

5474C

4

0.243

6.17

0.032

0.81

5475C

5

0.270

6.86

0.035

0.89

5476C

6

0.292

7.42

0.035

0.89

5477C

7

0.292

7.42

0.035

0.89

5478C

8

0.316

8.03

0.035

0.89

5479C

9

0.343

8.71

0.037

0.83

5480C

10

0.373

9.47

0.040

1.02

5480/15C

15

0.415

10.54

0.040

1.02

5480/19C

19

0.445

11.30

0.040

1.02

5480/25C

25

0.527

13.39

0.045

1.14

5480/50C *

50

0.699

17.75

0.053

1.35

*Color code chart C.

Individually Shielded, 22 AWG (0.35 mm

2

), 7/30 (7 x .025) Tinned Copper Drain Wire

UL VW-1

20 AWG (0.56 mm

2

)

Stranding: 7/28 (7 x 0.33 mm)

Insulation thickness: 0.010 (0.25 mm)

Part No.

Pairs

Nominal Diameter

Jacket Thickness

Inch

mm

Inch

mm

6416

2

0.295

7.49

0.041

1.04

Mutual capacitance: 55 pF/ft (180 pF/m)

Ground capacitance: 95 pF/ft (312 pF/m)

Advertising