MAINTENANCE/SERVICE


Cab Air System


COMPRESSOR PROTECTION
The compressor is protected from excessively low
suction and high discharge pressures by two
switches:

• Low suction pressure switch is located at the

outlet of the evaporator (under seat in cab). It
will close when the pressure drops below 4±2
psi and re-open when pressure rises above
20±5 psi.

• High discharge pressure switch is located on

the receiver drier (rear of tractor, behind right
side panel). It will close if pressure exceeds
325±10 psi and re-open when pressure drops
below 250±30 psi.



To prevent damage to the compressor, if the air
conditioning system is shut down by either switch,
locate the source of the problem and correct it
before operating the system.

REFRIGERANT OIL

Whenever the machine is first started after storage
for more than one week: Turn blower switch to
"OFF" and turn A/C temperature control switch to
maximum cooling. Start engine and operate at low
idle. Click blower switch from "OFF" to "LOW" for
one second, then back to "OFF" for 5 to 10
seconds. Repeat this cycle ten times to distribute
the oil throughout the system.

LOW SIDE

PRESSURE


HIGH

SIDE

PRESSURE


POSSIBLE
CAUSE


VERY

LOW


VERY

LOW


Lack of R134a


LOW


LOW


Loss of R134a
Restriction between condenser and drier


LOW


LOW

OR

NORMAL


Restriction between drier and expansion valve
Expansion valve plugged
Expansion valve stuck closed
Inoperative blower motor
Plugged filter or evaporator core
Moisture in system
Defective temperature control switch
Restriction at expansion valve
Restriction in evaporator
Restriction between evaporator and compressor suction


HIGH


LOW


Compressor belt slipping
Magnetic clutch slipping
Compressor internal failure


HIGH


HIGH


Condenser malfunction
Condenser coil plugged
Expansion valve stuck open
Restriction between compressor and condenser
Restriction inside condenser
Overcharge of refrigerant
Air in system


HIGH


NORMAL


Expansion valve stuck open


NORMAL


HIGH


Restriction between compressor and condenser
Restriction inside condenser
Overcharge of refrigerant


LOW


HIGH


Restriction between compressor and condenser
Restriction inside condenser

NOTE: Service ports are located on suction and discharge hoses at compressor.