RKI Instruments Beacon 100 User Manual

Page 19

Advertising
background image

Beacon 100 Gas Monitor Operator’s Manual

Alarm Indications • 19

2.

After the gas reading falls below the alarm 1 setpoint, press the reset switch to reset
the alarm 1 circuit. Resetting the alarm 1 circuit silences the buzzer, turns off the
ALARM 1 light, and de-energizes the alarm 1 relay.

NOTE:

To silence the buzzer while in an alarm 1 condition, press the reset switch.
You cannot de-energize the alarm 1 relay until the gas reading falls below (above
for oxygen) the alarm 1 setpoint. Once the gas reading falls below the alarm 1
setpoint, if the reset button has been previously pressed the alarm 1 relay will de-
energize.

Alarm 2 Condition

This section describes the audible and visual indications for an alarm 2 condition and
suggests response to an alarm 2 condition.

Alarm 2 condition indications

When the gas reading of an active channel reaches the alarm 2 setpoint, the Beacon senses
an alarm 2 condition. The Beacon 100 alerts you to an alarm 2 condition as follows:

the ALARM 2 light turns on

the gas reading in alarm 2 condition continues to flash

the buzzer sounds a faster pulsing tone than an alarm 1 condition

the alarm 2 relay energizes

Responding to an alarm 2 condition

This section suggests response to an alarm 2 condition.

1.

Follow your established procedure for a mid level combustible or toxic gas condition
or a severe decreasing oxygen content condition.

2.

After the gas reading falls below the alarm 2 setpoint, press the reset switch to reset
the alarm circuit. Resetting the alarm circuit turns off the ALARM 2 light, and
de-energizes the alarm 2 relay.

NOTE:

The alarm 2 condition cannot be silenced. The reset switch must be pressed after
the gas reading falls below the alarm 2 level in order to de-energize the alarm 2
relay.

Alarm 3 Condition

This section describes the audible and visual indications for an alarm 3 condition and
suggests response to an alarm 3 condition.

Alarm 3 condition indications

When the gas reading of an active channel reaches the alarm 3 setpoint, the Beacon 100
senses an alarm 3 condition. The Beacon 100 alerts you to an alarm 3 condition as follows:

the ALARM 3 light turns on

the gas reading in alarm 3 condition continues to flash (the gas reading for O

2

channels begins flashing)

the buzzer sounds a faster pulsing tone than an alarm 1 or alarm 2 condition

the alarm 3 relay energizes

Advertising