19 • Alarm Indications

Beacon 800 Gas Monitor Operator’s Manual

Alarm 1 Condition

This section describes the audible and visual indications for an alarm 1 condition and
suggests responses to an alarm 1 condition.

Alarm 1 Condition Indications

When the gas reading of an active channel reaches the alarm 1 setpoint, the Beacon 800
senses an alarm 1 condition. The Beacon 800 alerts you to an alarm 1 condition as
follows:

the ALARM 1 light turns on;

the gas reading in alarm 1 condition flashes and alternates with the ALARM-1
message;

the buzzer sounds a steady tone;

the common alarm 1 relay energizes;

the applicable alarm 1 channel relay energizes.

Responding to an Alarm 1 Condition

This section suggests the following responses to an alarm 1 condition:

1.

Follow your established procedure for a low-level combustible or toxic gas condition or
a decreasing oxygen condition.

2.

Oxygen alarms are factory set as self-resetting and will automatically clear when the
oxygen reading rises above the alarm 1 setpoint.

3.

Alarms for all other gas types are factory set as latching. After the gas reading falls
below (rises above for oxygen) the alarm 1 setpoint, press the reset switch to reset the
alarm 1 circuit. Resetting the alarm 1 circuit silences the buzzer, turns off the ALARM
1 light, resets the channel display, and de-energizes the common and channel alarm 1
relays.

NOTE: To silence the buzzer while in an alarm 1 condition, press the reset switch.

You cannot de-energize the alarm 1 relays until the gas reading falls below (rises
above for oxygen) the alarm 1 setpoint.

Alarm 2 Condition

This section describes the audible and visual indications for an alarm 2 condition and
suggests responses to an alarm 2 condition.

Alarm 2 Condition Indications

When the gas reading of an active channel reaches the alarm 2 setpoint, the Beacon 800
senses an alarm 2 condition. The Beacon 800 alerts you to an alarm 2 condition as
follows:

the ALARM 2 light turns on;

the gas reading during an alarm 2 condition continues to flash and alternates with the
ALARM-1 and ALARM-2 messages;

the buzzer sounds a steady tone;

the common alarm 2 relay energizes;

the applicable alarm 2 channel relay energizes.