Beacon 800 Gas Monitor Operator’s Manual

Internal Description • 6

Ground Stud

The ground stud is used for connecting earth ground to the Beacon 800. The ground stud
is factory wired to the GND terminal on the AC terminal strip. The ground stud is located in
the lower right corner of the main board.

Terminal Strips

The Beacon 800 includes four terminal strips for external wiring connections. See “Wiring
the Beacon 800 Gas Monitor” on page 12 for detailed wiring procedures.

Transmitter Terminal Strips

Two transmitter terminal strips are mounted to the bottom left corner of the main circuit
board (see Figure 1). These two 12-point terminal strips facilitate wiring connections to the
detector heads. The bottom terminal strip is for channels 1 through 4; the top terminal strip
is for channels 5 through 8.

Alarm Terminal Strips

Four alarm terminal strips are to the right of the transmitter terminal strips (see Figure 1).
These four 12-point terminal strips facilitate wiring connections to external alarm devices
(horn, strobe, etc.). The bottom row of alarm terminals is for alarm 1 connections; the top
row of alarm terminals is for alarm 2 connection.

NOTE: The alarm terminal strips provide external alarm connections controlled by

individual channels. The Beacon 800 also provides common alarm terminals on
the controller terminal strip. The common alarm terminals are controlled by all
active channels.

Controller Terminal Strip

The 19-point controller terminal strip is to the right of the alarm terminal strips (see Figure
1). The controller terminal strip facilitates various internal and external wiring connections.
Table 3 lists the function of each terminal.

Table 2: Beacon 800 Program Button Functions

Button

Function

ESCAPE

Moves backward through the Configuration Menu

Cancels changes you make in the Configuration Menu

Enters the Configuration Menu (press with ENTER button)

UP (YES)

Accepts the displayed setting and proceeds to the next setting

Changes the displayed setting

DOWN (NO)

Allows you to update the displayed setting

Changes the displayed setting

ENTER

Saves changes you make in the Configuration Menu

Enters the Configuration Menu (press with ESCAPE button)