Beacon 800 Gas Monitor Operator’s Manual

Troubleshooting • 30

Frequent or
Suspect
Alarms

The Beacon 800
alerts you to
frequent or suspect
alarms.

The transmitter’s
fresh air readings
remain on zero
(20.9 for oxygen).

The Beacon 800 is
experiencing false
readings due to RFI or
EMI.

The transmitter wiring
is disconnected,
misconnected, or
intermittent.

1. Verify that the transmitter wiring is

properly shielded.

2. Verify that the transmitter wiring is

correct and secure.

3. Verify that power and transmitter

wiring is routed through separate
conduit hubs on the bottom of the
Beacon 800 housing.

4. Increase the alarm on delay setting in

the Configuration menu.

5. If the frequent or suspect alarm

difficulties continue, contact RKI for
further instruction.

Flickering
Display

The display
readings flicker
often.

The Beacon 800 is
experiencing false
readings due to RFI or
EMI.

The noise filter setting
is too low.

The zero suppression
setting is too low.

The display screen is
malfunctioning.

1. Verify that the transmitter wiring is

properly shielded.

2. Verify that the transmitter wiring is

correct and secure.

3. Verify that power and transmitter

wiring is routed through separate
conduit hubs on the bottom of the
Beacon 800 housing.

4. Increase the noise filter setting in the

Configuration menu.

5. Increase the zero suppression setting

in the Configuration menu.

6. If the display difficulties continue,

contact RKI for further instruction.

Buzzer not
Working

The buzzer does not
sound an audible
alarm during alarm
conditions.

The buzzer sounds
weak or broken.

The buzzer is
disconnected or
misconnected.

The buzzer is
malfunctioning.

1. Verify that the wiring to the BUZ- and

BUZ+ terminals of the controller
terminal strip is correct and secure.

2. If the buzzer difficulties continue,

contact RKI for further instruction.

Reset Switch
not Working

The buzzer does not
silence when you
press the reset
switch.

The applicable
alarm circuit does
not reset when you
press the reset
switch after an
alarm condition
passes.

The reset switch is
disconnected or
misconnected.

The reset switch is
malfunctioning.

1. Verify that the wiring to the RESET (2)

terminals of the controller terminal
strip is correct and secure.

2. If the reset switch difficulties continue,

contact RKI for further instruction.

Table 9: Troubleshooting the Beacon 800 (Continued)

Condition

Symptom(s)

Probable Causes

Recommended Action