35-3001-04 Carbon Monoxide Sample-Draw Detector • 11

8.

Connect the wires to the applicable detector/transmitter terminal strip at the controller as
shown in Figure 6. Refer to the controller operator’s manual and the controller detector head
specification sheet for the 35-3001-04 for detector/terminal strip connections specific to the
controller.

Figure 6: Wiring the Sample-Draw Detector to a Controller

9.

If shielded cable is used, connect the cable’s drain wire to an available chassis (earth) ground at
the controller. RKI controllers typically have a ground stud that can be used to ground the
cable’s drain wire.

Not Used in

This Version

Blue (S)

Red (+)

OXY

LEL/IR

AMP 2

PATS201PATS201

AMP 1

+ 24 VDC

OXY

Controller or

Recording

Device

- (DC Ground)

4/20 Signal

LEL/ IR

AMP 2

AMP 1

PATS101PATS101