19 • Operation

Model GD-K77D

Operator’s Manual

Operation

Start-up Preparations

To avoid the possibility of electrical shock or damage to the Model GD-K77D, follow the
precautions listed below before turning on the unit:

Make sure the Model GD-K77D has been properly grounded.

Check all wiring connections to external devices.

Make sure the power voltage is within specification (DC-24V +/- 10%, Terminal
Voltage).

Check the wiring connections to any external alarms.

Make sure the correct dust filter has been properly installed.

CAUTION:

Because dust filters are designed for specific target gases, it is very important to
check whether the correct dust filter has been installed on the Model GD-K77D.

Check whether the Model GD-K77D’s fuse has the correct current and voltage.

Basic Operation Flow and Operating Modes

The diagram below shows the basic operation flow of the Model GD-K77D. There are
three basic operating modes:

Detection Mode (Normal operation)

Alarm Test Mode

Maintenance Mode

Figure 9: Operation Flow Chart

Start-up preparation

Power on

Initial clear (about 25 seconds)

Detection mode

Maintenance Mode 1 & 2

Alarm test mode

Test/set switch (press for about 3 seconds)

Mode, press for about 3 seconds