RKI Instruments GD-K77D User Manual

Page 31

Advertising
background image

Model GD-K77D

Operator’s Manual

Operation • 26

CAUTION:

The gas alarms will only work in Detection Mode. If the Model GD-K77D is left in
Maintenance Mode for ten hours or more, it will switch to Detection

Mode

automatically.

Alarm Point Confirmation

When checking the alarm point, follow these steps:

1.

With the front control cover of the Model GD-K77D flipped open, press and hold the
Mode switch for three seconds to start Maintenance Mode. The display will show 1-1
and the Skip light will flash.

2.

Select 1-2, Alarm Check Point by using the FLOW ADJ switch.

3.

Press the TEST/SET switch to display the Alarm Set-point. The ALM1 LED will flash.
The readings shown below are typical. Use the FLOW ADJ switch to display the
ALM2 set-point. The ALM2 LED will start flashing.

LED indication

Display indication

PW/TR

ALM1

ALM2

SKIP

1

1

LED indication

Display indication

PW/TR

ALM1

ALM2

SKIP

1

2

LED indication

Display indication

PW/TR

ALM1

ALM2

SKIP

PW/TR

ALM1

ALM2

SKIP

3.

0

0

6.

0

0