Maintenance mode – RKI Instruments GD-K77D User Manual

Page 28

Advertising
background image

23 • Operation

Model GD-K77D

Operator’s Manual

4-20mA Output

The following graph illustrates the relationship between the 4-20mA output and the gas
concentration.

Figure 10: 4-20 mA output vs. Gas Concentration

Maintenance Mode

There are two maintenance modes for the Model GD-K77D: Maintenance Mode 1 and
Maintenance Mode 2. Under Maintenance Mode 1, you can perform a zero adjustment
and confirm the alarm points. Under Maintenance Mode 2, you can confirm bias voltage
(optional), perform a zero adjustment, perform a span adjustment, and determine a
sensor’s start-up time. See “Calibration” under “Maintenance” for more information about
using Maintenance Mode 2.

To activate Maintenance Mode, remove the Model GD-K77D’s cover, then press and hold
the Mode switch for three (3) seconds.

0

External output

Gas
Concentration

22mA
20mA

Maintenance mode

6% of full scale
zero suppression

2.5 mA

4 mA

Full

Scale

Measuring mode