Operator’s Manual

Operation • 24

Maintenance Mode Operation Flow

CAUTION:

When Maintenance Mode is entered during a gas alarm, the alarm condition will be cancelled.
The relay contact will be reset and the 4-20 mA output will lock on 2.5 mA.

Zero Adjustment

A zero adjustment resets the Model GD-K77D’s gas detecting system to zero so it can
accurately sample the target gas. This test should be done periodically, such as once a
month. This procedure illustrates how to use the zero function in Maintenance Mode 1. If a
full calibration is being done, use the zero function in Maintenance Mode 2 (see calibration
section).

PW/TR

ALM1

ALM2

SKIP

PW/TR

ALM1

ALM2

SKIP

LED indication

Display indication

PW/TR

ALM1

ALM2

SKIP

PW/TR

ALM1

ALM2

SKIP

Press mode switch for

three seconds

Maintenance mode starts

1-1 Zero Adjustment

1-2 Alarm points

1-3 Maintenance mode 2

FLOW ADJ/select by

▲ ▼

SW

Maintenance Mode 1

FLOW ADJ/select by

▲ ▼

SW