37

MAIN BURNER LIGHTS

SPARK STOPS WHEN
BURNER LIT.

DOES FLAME REMAIN
STABLE AFTER THE
SPARK CYCLE IS COM-
PLETE. (NO FLAME FAIL)

*

CHECK FOR CORRECT MANIFOLD GAS PRESSURE

*CHECK FOR OBSTRUCTION IN GAS SUPPLY OR

ORIFICE (INSECTS, SPIDERS COCOONS ETC.)

CHECK SENSOR FLAME SIGNAL WITH METER FOR

0.7µA MINIMUM STEADY READING.

IF READING IS LOW CHECK GAS PRESSURE
IF OK .....CHANGE SENSOR.

CHECK FOR CONTINUITY OR SENSOR CABLE AND
GROUND WIRE.

CHECK THAT BURNER FLAME COVERS ALL ELEC-
TRODES. IF CHECKS ARE OKAY, REPLACE CONTROL

MODULE.
NOTE: IF GROUND IS POOR OR ERRATIC, SHUT-

DOWN MAY OCCUR OCCASIONALLY EVEN THOUGH
OPERATION IAPPEARS NORMAL AT THE TIME.

CHECK FOR PROPER TEMPERATURE CONTROLLER

OPERATION.

CHECK SENSOR FLAME SIGNAL WITH METER FOR
0.7µA MINIMUM STEADY READING.(REPEAT ABOVE)

CALL FOR HEAT ENDS;
SYSTEM SHUTS OFF

TROUBLE SHOOTING ENDS

NOTE: IF CONTROL GOES INTO LOCKOUT, THE SYSTEM CAN BE

RESET BY INTERRUPTING THE POWER SOURCE

NO

YES

YES

NO

YES

NO

NO

CHECK FLAME SIGNAL WITH METER FOR 0.7µA.

IF READING IS LOW CHECK GAS PRESSURE, IF OK

CHANGE SENSOR.
CHECK FOR CONTINUITY OR SENSOR CABLE AND

GROUND WIRE.
CHECK THAT BURNER FLAME COVERS ALL ELEC-

TRODES.
IF CHECKS ARE OKAY, REPLACE CONTROL MODULE.

SYSTEM RUNS UNTIL
CALL FOR HEAT ENDS

CHECK AND ADJUST TEMPERATURE CONTROLLER

SETTING AND CHECK CONTROLLER CONNECTIONS

CHECK FOR PINCHED WIRING.
REMOVE VALVE LEAD AT CONTROL IF VALVE

CLOSES, RECHECK TEMPERATURE CONTROLLER
AND WIRING;

IF VALVE DOES NOT CLOSE REPLACE GAS VALVE.

YES