GAS REQUIREMENTS AND LEAK TESTING:

NATURAL GAS:

NEVER CONNECT AN UNREGULATED GAS SUPPLY TO THE HEATER.
This heater requires a natural gas pressure regulator (not supplied)



PRECAUTIONS:

· Periodically check the whole system for leaks or if the smell of gas is detected.
· Extinguish all open flames.
· Never smoke while leak testing.
· If you can not stop a leak, turn off the gas supply and call a qualified and licensed techni-

cian, or your gas supplier.

· Only those parts recommended by the Manufacturer should be used. Substitution will void

the warranty.

· Do not use the heater until all connections have been leak tested and are sound !!!


GAS REQUIREMENTS:

· Maximum inlet pressure to heater must not exceed 5” w.c.
· Heater manifold pressure required to maintain correct burner input is 5” w.c.
· The installation must conform with local codes, or in the absence of local codes, with Na-

tional Fuel Gas Code.

3.1 Series 4SN5/4BN6 specifications:

· Manifold pressure 5” w.c. maximum / 2” w.c. minimum

· Maximum Inlet gas supply pressure 5” w.c.

· Maximum operating input rating

38,000 BTUH @ 5” w.c.


· Low fire input rating

22,000 BTUH @ 2” w.c.


· Effective radiant range

8 to 20 foot circle (affected by wind and ambient

temperature)
· Fuel

N.G.


· Net Weight

60 lbs .


· Certification

CSA International US and Canada