Schwank sportSchwank User Manual

Page 7

Advertising
background image

sportSchwank Manual

IM080731

RD: July 2008

RL: 01A

BA

2.2 HEATER MOUNTING

The sportSchwank Series heater is approved for both horizontal and angle mounting.
When angle mounting, the short axis may be rotated to a maximum of 30°. Refer to
FIGURE 3. Improper angle mounting can result in damage to the heater and unsafe or
uncertain operation, and will void warranty.

IMPORTANT: For either horizontal or angle mounting, the long axis of the heater must
be level. Use only non-combustible mounting hardware. FIGURE 2 on Page 5 illus-
trates typical suspension hardware that may be used.

Maintain adequate clearance around air openings into the combustion chamber, clear-
ances from combustible material, provision for accessibility, and for combustion and
ventilating air supply.



2.3 SERVICE ACCESS CLEARANCE

FIGURE 1









Refer to Section 16 for complete Service Access instruction

2.3 GAS SUPPLY LINE INSTALLATION



All piping must be installed according to local codes or, in the absence of local
codes, with the National Fuel Gas Code ANSI Z223.1/ NFPA 54 in the USA, or in
Canada the Natural Gas and Propane Installation Code, CSA B149.1, or the Pro-
pane Storage and Handling Code
, B149.2..



A drip-pocket at the inlet connection must be provided.



Piping joint compounds must be resistant to the action of liquefied petroleum gases.



Ensure gas pipe is sized to meet the capacity requirements of all heaters in the sys-
tem, and the supply pressure requirements outlined in Section 2.5 below.



DO NOT INSTALL ANY GAS PIPING IN HEAT ZONES

2.4 PRESSURE AND GAS LEAK TESTING

Test the gas supply piping system for leaks:



Test piping joints for leaks with a soap and water solution



Test piping system for leaks using gas meter / pressure gage test.

Page 4

Advertising