Schwank STSp-USA User Manual

Page 10

Advertising
background image

SP-MSTP-AU-05A

STS-p Manual

RD: DEC, 2003

RL: 5

KH

7. SYSTEMS INCORPORATING 90

O

ELBOWS AND 180

O

ELBOWS

The STS-p Series radiant tube heater can be
installed in configurations as illustrated in
FIGURE 2. (below) with a maximum of two
90

o

or one 180

o

elbow per heater. The use of

radiant elbows reduces the total maximum
vent allowable. See SECTION 10 (PAGE
15): Re: Flue venting.

Both the 90

o

and 180

o

elbows are shipped as a

kit with one coupler and two end plate hangers
to close off the reflector ends each side of the
elbow (s). The Reflectors must be secured
with four screws to each of the end plate
hangers, See FIG 3 (PAGE 7) and FIG: 6
(PAGE 8).

On Models STS-p 200 and 175, a
minimum of 30’ of straight radiant
tube must be connected to the burner
before any elbow. On Models 155,130
and 110, a minimum of 20’ of straight
Radiant tube must be connected to

FIGURE 2 SYSTEM CONFIGURATIONS

System Configuration
1 Straight line
2 “U” tube with 180 degree elbow kit
3 “L” tube with 90 degree elbow kit
4 Twinned tubes into common TEE flue vent

Venting Options
A Flue Vent through wall 4”
B Flue Vent through wall or roof 6”
C Flue vent through roof
D Flue Vent into building, exhaust fan

interlocked with heater

E Combustion air intake from outside

through wall

F Combustion air intake from outside

through roof

G Combustion air intake from inside build-

ing

A

F

C

G

D

E

B

1

2

3

4

G

G

the burner before any elbow. And
on Models STS-p 80, 60 and 45, a
minimum of 10' of straight
radiant tube must be connected to
the burner before any elbow.

IMPORTANT:

Page 6

Advertising