Gas requirements and leak testing: natural gas – Schwank 4N/L62-J Pole Mounted User Manual

Page 5

Advertising
background image

GP-M45J-CX-03D

4N/L51-J,4N/L62-J Manual

RD: Aug 2006

RL: 3D

KH

GAS REQUIREMENTS AND LEAK TESTING:

NATURAL GAS:

NEVER CONNECT AN UNREGULATED GAS SUPPLY TO THE HEATER.
This heater requires a natural gas pressure regulator (not supplied)



PRECAUTIONS:

• Periodically check the whole system for leaks or if the smell of gas is detected.

• Extinguish all open flames.

• Never smoke while leak testing.

• If you can not stop a leak, turn off the gas supply and call a qualified and licensed technician, or

your gas supplier.

• Only those parts recommended by the Manufacturer should be used. Substitution will void the

warranty.

Do not use the heater until all connections have been leak tested and are sound !!!


GAS REQUIREMENTS:

• Maximum inlet pressure to heater must not exceed 5” w.c.

• Heater manifold pressure required to maintain correct burner input is 5” w.c.

• The installation must conform with local codes, or in the absence of local codes, with National Fuel

Gas Code.

3.1 Series 4N51/62, 44N5/6 specifications:

• Manifold pressure 5” w.c. maximum / 2” w.c. minimum

• Maximum Inlet gas supply pressure 5” w.c.

• Maximum operating input rating 45,000 BTUH @ 5” w.c.

• Low fire input rating 24,000 BTUH @ 2” w.c.

• Effective radiant range 8 to 20 foot circle (affected by wind and ambient
temperature)
• Fuel N.G.

• Net Weight 60 lbs .

• Certifications CSA International US and Canada


Page 2

Advertising
This manual is related to the following products: