Installation – Regency Horizon HZ54E Large Gas Fireplace User Manual

Page 25

Advertising
background image

Regency Horizon HZ54E-1 Gas Fireplace

25

INSTALLATION

• Vent must be supported at offsets.
• Firestops are required at each fl oor level and

whenever passing through a wall.

• Maintain clearances to combustibles as listed in

the "Clearances" section.

• Refer to the "Vent Restrictor Position" section

for details on how to change the vent restrictor
from the factory setting of Set 1 to Set 2 or Set 4
if required.

Note: Must use optional fl ue adaptor when using

Rigid Pipe (Part # 770-994).

Maximum: 40 ft. (12.2m)

Minimum

8’6”

(2.6m)

Min. 44”

(1

1

18mm)

Max. 10’ (3m)(centerline to centerline)

Minimum length of pipe

between elbows 12” (305mm)

Maximum: 27 ft. (8.2m)

0

2

4

6

40

8

10

12

14

16

18

20

22

24

26

28

30

V

ertical Height (Feet)

32

34

36

38

6

8

Horizontal (Feet)

2

0

4

10

12

12

16

18

14

20

Vent Restrictor on Set 2

Vent Restrictor on Set 4

Vent Restrictor on Set 1

(factory setting)

VENTING ARRANGEMENTS

ALLOWABLE VERTICAL TERMINATIONS FOR HZ54E-NG

The shaded area in the diagram shows all allowable
combinations of straight vertical and offset to vertical
terminations, using two 90

o

elbows, with Rigid Pipe Venting

Systems for Natural Gas. Two 45

o

elbows equal to one 90

o

elbow. Maximum of four 45

o

elbows allowed.

Please note min. 1 foot between 90

o

elbows is required.