Installation – Regency Horizon HZ54E Large Gas Fireplace User Manual

Page 26

Advertising
background image

26

Regency Horizon HZ54E-1 Gas Fireplace

INSTALLATION

• Vent must be supported at offsets.
• Firestops are required at each fl oor level and

whenever passing through a wall.

• Maintain clearances to combustibles as listed in

the "Clearances" section.

Refer to the "Vent Restrictor Position" section for
details on how to change the vent restrictor from
the factory setting of Set 1 to Set 4 or Set 5

if

required.

Note: Must use optional fl ue adaptor when using

Rigid Pipe (Part # 770-994).

Maximum: 40 ft. (12.2m)

Minimum

8’6”

(2.6m)

Min. 44”

(1

1

18mm)

Max. 10’ (3m)(centerline to centerline)

Maximum: 27 ft. (8.2m)

0

2

4

6

40

8

10

12

14

16

18

20

22

24

26

28

30

V

ertical Height (Feet)

32

34

36

38

6

8

Horizontal (Feet)

2

0

4

10

12

12

16

18

14

20

Vent Restrictor on Set 4

Vent Restrictor on Set 5

Vent Restrictor on Set 1

(factory setting)

Minimum length of pipe

between elbows 12” (305mm)

VENTING ARRANGEMENTS

ALLOWABLE VERTICAL TERMINATIONS FOR HZ54E-LP

The shaded area in the diagram shows all allowable
combinations of straight vertical and offset to vertical
terminations, using two 90

o

elbows, with Rigid Pipe Venting

Systems for Propane. Two 45

o

elbows equal to one 90

o

elbow. Maximum of four 45

o

elbows allowed.

Please note min. 1 foot between 90

o

elbows is required.